HHeadroomLower tier COMAH site

What can I take

How much more of each substance the site could safely accept, and which tank it should go in.

Headroom is the room left before crossing into upper tier.

  • Gas oil (distillate marine diesel)752.7 t
    Limited by tank spaceBest tank TK-104 (700 t)
    How this was worked out

    The tanks are physically full.

    1. Physical capacity700 tThis one applies

      TK-104 holds 900,000 kg of 1,600,000 kg working capacity.

      Site asset register — declared working capacity

    2. Aggregate threshold1,850 t

      Environmental hazards (Section E) sum is at 0.926 of the upper tier threshold. Remaining fraction 0.074 × qualifying quantity 25,000 t = 1,850 t before the site reaches upper tier on this group.

      COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 2 — named substances take precedence over Part 1 categories

    3. Segregationno limit

      No compatibility rule is engaged by this substance in this zone.

      No compatibility rule engaged

  • Toluene752.7 t
    Limited by tank spaceBest tank TK-104 (700 t)
    How this was worked out

    The tanks are physically full.

    1. Physical capacity700 tThis one applies

      TK-104 holds 900,000 kg of 1,600,000 kg working capacity.

      Site asset register — declared working capacity

    2. Aggregate threshold7,450 t

      Physical hazards (Section P + O) sum is at 0.851 of the upper tier threshold. Remaining fraction 0.149 × qualifying quantity 50,000 t = 7,450 t before the site reaches upper tier on this group.

      COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 1, entry P5c

    3. Segregationno limit

      No compatibility rule is engaged by this substance in this zone.

      No compatibility rule engaged

  • Methanol745 t
    Limited by the COMAH thresholdBest tank TK-101 (580 t)
    How this was worked out

    Taking more would push the site over a COMAH threshold.

    1. Physical capacity580 tThis one applies

      TK-101 holds 620,000 kg of 1,200,000 kg working capacity.

      Site asset register — declared working capacity

    2. Aggregate threshold745 t

      Physical hazards (Section P + O) sum is at 0.851 of the upper tier threshold. Remaining fraction 0.149 × qualifying quantity 5,000 t = 745 t before the site reaches upper tier on this group.

      COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 2 — named substances take precedence over Part 1 categories

    3. Segregationno limit

      No compatibility rule is engaged by this substance in this zone.

      No compatibility rule engaged

  • Sodium hypochlorite solution 14%37 t
    Limited by the COMAH thresholdBest tank VS-301 (37 t)
    How this was worked out

    Taking more would push the site over a COMAH threshold.

    1. Aggregate threshold37 tThis one applies

      Environmental hazards (Section E) sum is at 0.926 of the upper tier threshold. Remaining fraction 0.074 × qualifying quantity 500 t = 37 t before the site reaches upper tier on this group.

      COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 2 — named substances take precedence over Part 1 categories

    2. Physical capacity40 t

      VS-301 holds 20,000 kg of 60,000 kg working capacity.

      Site asset register — declared working capacity

    3. Segregationno limit

      No compatibility rule is engaged by this substance in this zone.

      No compatibility rule engaged

  • Dibenzoyl peroxide paste (Type C)29.8 t
    Limited by the COMAH thresholdBest tank VS-301 (29.8 t)
    How this was worked out

    Taking more would push the site over a COMAH threshold.

    1. Aggregate threshold29.8 tThis one applies

      Physical hazards (Section P + O) sum is at 0.851 of the upper tier threshold. Remaining fraction 0.149 × qualifying quantity 200 t = 29.8 t before the site reaches upper tier on this group.

      COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 1, entry P6b

    2. Physical capacity40 t

      VS-301 holds 20,000 kg of 60,000 kg working capacity.

      Site asset register — declared working capacity

    3. Segregationno limit

      No compatibility rule is engaged by this substance in this zone.

      No compatibility rule engaged

  • Hydrogen peroxide 60%29.8 t
    Limited by the COMAH thresholdBest tank TK-201 (29.8 t)
    How this was worked out

    Taking more would push the site over a COMAH threshold.

    1. Aggregate threshold29.8 tThis one applies

      Physical hazards (Section P + O) sum is at 0.851 of the upper tier threshold. Remaining fraction 0.149 × qualifying quantity 200 t = 29.8 t before the site reaches upper tier on this group.

      COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 1, entry P8

    2. Physical capacity260 t

      TK-201 holds 240,000 kg of 500,000 kg working capacity.

      Site asset register — declared working capacity

    3. Segregationno limit

      No compatibility rule is engaged by this substance in this zone.

      No compatibility rule engaged

  • Nitric acid 68%29.8 t
    Limited by the COMAH thresholdBest tank VS-301 (29.8 t)
    How this was worked out

    Taking more would push the site over a COMAH threshold.

    1. Aggregate threshold29.8 tThis one applies

      Physical hazards (Section P + O) sum is at 0.851 of the upper tier threshold. Remaining fraction 0.149 × qualifying quantity 200 t = 29.8 t before the site reaches upper tier on this group.

      COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 1, entry P8

    2. Physical capacity40 t

      VS-301 holds 20,000 kg of 60,000 kg working capacity.

      Site asset register — declared working capacity

    3. Segregationno limit

      No compatibility rule is engaged by this substance in this zone.

      No compatibility rule engaged

  • Propane (commercial LPG)29.8 t
    Limited by the COMAH thresholdBest tank TK-201 (29.8 t)
    How this was worked out

    Taking more would push the site over a COMAH threshold.

    1. Aggregate threshold29.8 tThis one applies

      Physical hazards (Section P + O) sum is at 0.851 of the upper tier threshold. Remaining fraction 0.149 × qualifying quantity 200 t = 29.8 t before the site reaches upper tier on this group.

      COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 2 — named substances take precedence over Part 1 categories

    2. Physical capacity260 t

      TK-201 holds 240,000 kg of 500,000 kg working capacity.

      Site asset register — declared working capacity

    3. Segregationno limit

      No compatibility rule is engaged by this substance in this zone.

      No compatibility rule engaged

  • Ammonia, anhydrous14.8 t
    Limited by the COMAH thresholdBest tank VS-302 (14.8 t)
    How this was worked out

    Taking more would push the site over a COMAH threshold.

    1. Aggregate threshold14.8 tThis one applies

      Environmental hazards (Section E) sum is at 0.926 of the upper tier threshold. Remaining fraction 0.074 × qualifying quantity 200 t = 14.8 t before the site reaches upper tier on this group.

      COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 2 — named substances take precedence over Part 1 categories

    2. Physical capacity50 t

      VS-302 holds 40,000 kg of 90,000 kg working capacity.

      Site asset register — declared working capacity

    3. Segregationno limit

      No compatibility rule is engaged by this substance in this zone.

      No compatibility rule engaged

  • Copper(II) sulphate solution 25%14.8 t
    Limited by the COMAH thresholdBest tank TK-101 (14.8 t)
    How this was worked out

    Taking more would push the site over a COMAH threshold.

    1. Aggregate threshold14.8 tThis one applies

      Environmental hazards (Section E) sum is at 0.926 of the upper tier threshold. Remaining fraction 0.074 × qualifying quantity 200 t = 14.8 t before the site reaches upper tier on this group.

      COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 1, entry E1

    2. Physical capacity580 t

      TK-101 holds 620,000 kg of 1,200,000 kg working capacity.

      Site asset register — declared working capacity

    3. Segregationno limit

      No compatibility rule is engaged by this substance in this zone.

      No compatibility rule engaged

  • Acrylonitrile3.4 t
    Limited by tank spaceBest tank TK-101 (500 kg)
    How this was worked out

    The tanks are physically full.

    1. Segregation500 kgThis one applies

      SEG-07 Acute toxics separated from flammable liquids. Methanol is held in the same zone and separation cannot be demonstrated, so this substance is capped at the rule's 500 kg de minimis quantity.

      HSG71 §Segregation of incompatible materials; COMAH SPC Technical Measures — segregation

    2. Aggregate threshold14.8 t

      Environmental hazards (Section E) sum is at 0.926 of the upper tier threshold. Remaining fraction 0.074 × qualifying quantity 200 t = 14.8 t before the site reaches upper tier on this group.

      COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 2 — named substances take precedence over Part 1 categories

    3. Physical capacity580 t

      TK-101 holds 620,000 kg of 1,200,000 kg working capacity.

      Site asset register — declared working capacity