What can I take
How much more of each substance the site could safely accept, and which tank it should go in.
Headroom is the room left before crossing into upper tier.
- Methanol772 tLimited by the COMAH thresholdBest tank TK-101 (580 t)
How this was worked out
Taking more would push the site over a COMAH threshold.
- Physical capacity580 tThis one applies
TK-101 holds 620,000 kg of 1,200,000 kg working capacity.
Site asset register — declared working capacity
- Aggregate threshold772 t
Physical hazards (Section P + O) sum is at 0.846 of the upper tier threshold. Remaining fraction 0.154 × qualifying quantity 5,000 t = 772 t to stay below upper tier on this group.
COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 2 — named substances take precedence over Part 1 categories
- Segregationno limit
No compatibility rule is engaged by this substance in this zone.
No compatibility rule engaged
- Gas oil (distillate marine diesel)700 tLimited by tank spaceBest tank TK-104 (700 t)
How this was worked out
The tanks are physically full.
- Physical capacity700 tThis one applies
TK-104 holds 900,000 kg of 1,600,000 kg working capacity.
Site asset register — declared working capacity
- Aggregate threshold1,850 t
Environmental hazards (Section E) sum is at 0.926 of the upper tier threshold. Remaining fraction 0.074 × qualifying quantity 25,000 t = 1,850 t to stay below upper tier on this group.
COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 2 — named substances take precedence over Part 1 categories
- Segregationno limit
No compatibility rule is engaged by this substance in this zone.
No compatibility rule engaged
- Toluene320 tLimited by tank spaceBest tank TK-103 (320 t)
How this was worked out
The tanks are physically full.
- Physical capacity320 tThis one applies
TK-103 holds 1,180,000 kg of 1,500,000 kg working capacity.
Site asset register — declared working capacity
- Aggregate threshold7,720 t
Physical hazards (Section P + O) sum is at 0.846 of the upper tier threshold. Remaining fraction 0.154 × qualifying quantity 50,000 t = 7,720 t to stay below upper tier on this group.
COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 1, entry P5c
- Segregationno limit
No compatibility rule is engaged by this substance in this zone.
No compatibility rule engaged
- Propane (commercial LPG)30.9 tLimited by the COMAH thresholdBest tank VS-301 (30.9 t)
How this was worked out
Taking more would push the site over a COMAH threshold.
- Aggregate threshold30.9 tThis one applies
Physical hazards (Section P + O) sum is at 0.846 of the upper tier threshold. Remaining fraction 0.154 × qualifying quantity 200 t = 30.9 t to stay below upper tier on this group.
COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 2 — named substances take precedence over Part 1 categories
- Physical capacity40 t
VS-301 holds 20,000 kg of 60,000 kg working capacity.
Site asset register — declared working capacity
- Segregationno limit
No compatibility rule is engaged by this substance in this zone.
No compatibility rule engaged
- Ammonia, anhydrous14.8 tLimited by the COMAH thresholdBest tank VS-302 (14.8 t)
How this was worked out
Taking more would push the site over a COMAH threshold.
- Aggregate threshold14.8 tThis one applies
Environmental hazards (Section E) sum is at 0.926 of the upper tier threshold. Remaining fraction 0.074 × qualifying quantity 200 t = 14.8 t to stay below upper tier on this group.
COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 2 — named substances take precedence over Part 1 categories
- Physical capacity50 t
VS-302 holds 40,000 kg of 90,000 kg working capacity.
Site asset register — declared working capacity
- Segregationno limit
No compatibility rule is engaged by this substance in this zone.
No compatibility rule engaged
- Copper(II) sulphate solution 25%10 tLimited by tank spaceBest tank RB-501 (10 t)
How this was worked out
The tanks are physically full.
- Physical capacity10 tThis one applies
RB-501 holds 30,000 kg of 40,000 kg working capacity.
Site asset register — declared working capacity
- Aggregate threshold14.8 t
Environmental hazards (Section E) sum is at 0.926 of the upper tier threshold. Remaining fraction 0.074 × qualifying quantity 200 t = 14.8 t to stay below upper tier on this group.
COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 1, entry E1
- Segregationno limit
No compatibility rule is engaged by this substance in this zone.
No compatibility rule engaged
- Dibenzoyl peroxide paste (Type C)10 tLimited by tank spaceBest tank RB-501 (10 t)
How this was worked out
The tanks are physically full.
- Physical capacity10 tThis one applies
RB-501 holds 30,000 kg of 40,000 kg working capacity.
Site asset register — declared working capacity
- Aggregate threshold30.9 t
Physical hazards (Section P + O) sum is at 0.846 of the upper tier threshold. Remaining fraction 0.154 × qualifying quantity 200 t = 30.9 t to stay below upper tier on this group.
COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 1, entry P6b
- Segregationno limit
No compatibility rule is engaged by this substance in this zone.
No compatibility rule engaged
- AcrylonitrileNoneBlocked — a tank too close by
How this was worked out
A nearby tank holds something this cannot be stored close to.
- Segregation0 kgThis one applies
SR-07 Acute toxics separated from flammable liquids. Methanol is held in the same zone and separation cannot be demonstrated, so adding any Acrylonitrile here would create a breach.
HSG71 §Segregation of incompatible materials; COMAH SPC Technical Measures — segregation
- Physical capacity0 kg
TK-101 is in service for Methanol, not Acrylonitrile, so it offers no capacity for this substance.
Site asset register — zone service allocation
- Aggregate threshold14.8 t
Environmental hazards (Section E) sum is at 0.926 of the upper tier threshold. Remaining fraction 0.074 × qualifying quantity 200 t = 14.8 t to stay below upper tier on this group.
COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 2 — named substances take precedence over Part 1 categories
- Hydrogen peroxide 60%NoneBlocked — a tank too close by
How this was worked out
A nearby tank holds something this cannot be stored close to.
- Segregation0 kgThis one applies
SR-01 Oxidising liquids/solids separated from flammable liquids. Methanol is held in the same zone and separation cannot be demonstrated, so adding any Hydrogen peroxide 60% here would create a breach.
HSG71 §Segregation of incompatible materials, Table 2; CLP Annex I classes 2.13 / 2.6
- Physical capacity0 kg
TK-101 is in service for Methanol, not Hydrogen peroxide 60%, so it offers no capacity for this substance.
Site asset register — zone service allocation
- Aggregate threshold30.9 t
Physical hazards (Section P + O) sum is at 0.846 of the upper tier threshold. Remaining fraction 0.154 × qualifying quantity 200 t = 30.9 t to stay below upper tier on this group.
COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 1, entry P8
- Nitric acid 68%NoneBlocked — a tank too close by
How this was worked out
A nearby tank holds something this cannot be stored close to.
- Segregation0 kgThis one applies
SR-01 Oxidising liquids/solids separated from flammable liquids. Methanol is held in the same zone and separation cannot be demonstrated, so adding any Nitric acid 68% here would create a breach.
HSG71 §Segregation of incompatible materials, Table 2; CLP Annex I classes 2.13 / 2.6
- Physical capacity0 kg
TK-101 is in service for Methanol, not Nitric acid 68%, so it offers no capacity for this substance.
Site asset register — zone service allocation
- Aggregate threshold30.9 t
Physical hazards (Section P + O) sum is at 0.846 of the upper tier threshold. Remaining fraction 0.154 × qualifying quantity 200 t = 30.9 t to stay below upper tier on this group.
COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 1, entry P8
- Sodium hypochlorite solution 14%NoneBlocked — a tank too close by
How this was worked out
A nearby tank holds something this cannot be stored close to.
- Segregation0 kgThis one applies
SR-10 Active-chlorine releasing substances separated from flammable liquids. Methanol is held in the same zone and separation cannot be demonstrated, so adding any Sodium hypochlorite solution 14% here would create a breach.
HSG95 §Hypochlorite storage; HSG71 Table 2
- Physical capacity0 kg
TK-101 is in service for Methanol, not Sodium hypochlorite solution 14%, so it offers no capacity for this substance.
Site asset register — zone service allocation
- Aggregate threshold37 t
Environmental hazards (Section E) sum is at 0.926 of the upper tier threshold. Remaining fraction 0.074 × qualifying quantity 500 t = 37 t to stay below upper tier on this group.
COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule; COMAH 2015 Sch. 1 Pt. 2 — named substances take precedence over Part 1 categories