2 tank pairs are too close
Lower tier COMAH site · 1 to keep an eye on
Closest COMAH limit
Close enough that a large delivery could cross the threshold. Run an intake check before accepting.
Other 2 categories
COMAH 2015 Sch. 1 Pt. 3, Note 4 — summation rule
What you can take today
- Gas oil (distillate marine diesel)752.7 t
- Toluene752.7 t
- Methanol745 t
- Sodium hypochlorite solution 14%37 t
- Dibenzoyl peroxide paste (Type C)29.8 t
Tanks stored too close together
- Fix
Acrylonitrile DS-401 is in the same zone as Hydrogen peroxide 60% DS-401
These two cannot share a zone. Move one to another tank.
Why this rule applies
Oxidising liquids/solids separated from flammable liquidsSEG-01Both substances are held in DS-401 with no internal separation. An oxidiser release into a flammable liquid pool supplies oxygen to the fire, defeating foam and vapour suppression.
- Measured
- same zone
- Required
- 5 m or separate compartment
HSG71 §Segregation of incompatible materials, Table 2; CLP Annex I classes 2.13 / 2.6
- Fix
Sodium hypochlorite solution 14% TK-201 is 6 m from Nitric acid 68% TK-202
4 m short of the 10 m needed or put in a separate compartment.
Why — 2 rules apply
Active-chlorine releasing substances separated from acidsSEG-05StrictestTK-201 and TK-202 are 6 m apart with independent bunding between them. Mixing hypochlorite with acid liberates chlorine gas immediately and in quantity; a shared bund is a mixing path, not a barrier.
- Measured
- 6 m · independent bunding
- Required
- 10 m or separate compartment
HSG71 §Segregation of incompatible materials, Table 2; HSG95 §Hypochlorite storage
Corrosive acids separated from corrosive alkalisSEG-06TK-201 and TK-202 are 6 m apart with independent bunding between them. Neutralisation is violent and exothermic at bulk scale, with aerosol generation and containment damage.
- Measured
- 6 m · independent bunding
- Required
- 10 m or separate compartment
HSG71 §Segregation of incompatible materials, Table 2
- Watch
Nitric acid 68% TK-202 is 11 m from Ammonia, anhydrous VS-302
Meets the 10 m minimum, but only by 1 m. No room to move stock closer.
Why this rule applies
Corrosive acids separated from corrosive alkalisSEG-06TK-202 and VS-302 are 11 m apart with open ground between them. Neutralisation is violent and exothermic at bulk scale, with aerosol generation and containment damage.
- Measured
- 11 m · open ground
- Required
- 10 m or separate compartment
HSG71 §Segregation of incompatible materials, Table 2
Northgate Bulk Storage Ltd · inventory as of 05 Aug 2026 · 10 zones · 3,712 t held against 6,030 t capacity